Every observation on an Electrical Installation Condition Report carries one of four classification codes (BS 7671:2018+A2:2022 model form, Section K). The code tells the person responsible for the installation how urgent the remedial action is.

C1 — Danger present. Risk of injury. Immediate remedial action required.

Users are at risk now. Typical examples: exposed live parts at a broken accessory, a socket or switch that can be touched live, conductors accessible without tools, equipment still energised with a burnt or arcing connection.

Wherever practicable the inspector should make it safe on discovery; if that is not possible, the person ordering the work gets urgent written notification.

C2 — Potentially dangerous. Urgent remedial action required.

The installation may become dangerous, or does not provide the required protection. Typical examples: no RCD protection for socket-outlets or other circuits requiring additional protection, absent or ineffective main protective bonding, undersized or damaged earthing conductor, a consumer unit with damaged enclosure or signs of thermal damage, absent polarity confirmation.

C2 items must be rectified as a matter of urgency — for landlords that feeds the 28-day written-confirmation duty.

C3 — Improvement recommended.

Safe for continued use, but not to the full current edition of BS 7671. Typical examples: bonding conductor sizes below today's Table 54.8 values, missing RCD six-monthly test notice, older accessories with no RCD where the exception is permitted, labelling gaps.

C3 codes do not make the report Unsatisfactory. An installation with only C3s is Satisfactory — treat them as a punch list, not a defect.

FI — Further investigation required without delay.

The inspection revealed an apparent deficiency that could not be fully identified because of the agreed extent and limitations — and which could reveal a C1 or C2 once examined. Typical examples: a circuit that cannot be traced, suspected concealed cable damage in a zone that could not be verified, an inaccessible consumer unit interior.

FI always results in an Unsatisfactory assessment, because the inspector could not verify the installation fully.

Other marks you will see on the schedules

MarkMeaning
✓ (tick)Acceptable condition — item inspected and compliant.
N/VNot verified — the item could not be verified (e.g. concealed cables within agreed limitations).
LIMLimitation — inspection limited by the agreed extent in Section D.
N/ANot applicable — e.g. no earth electrode present.
XUsed on intake equipment (Section 1) where an inadequacy is found — must be backed by a comment in Section K.

The Satisfactory / Unsatisfactory rule

It is binary — there is no weighting or averaging:

Our EICR generator applies this rule automatically as you code observations and schedule items, so the assessment in Section E can never contradict your findings — you can still override it manually.

Landlord duties after an Unsatisfactory report

FAQ

What does C1 mean on an EICR?
C1 — Danger present. Risk of injury. Immediate remedial action is required. Examples: exposed live conductors, a socket or switch that can give an electric shock, burnt-out accessory still in service. Wherever practicable a C1 is made safe on discovery.
What does C2 mean on an EICR?
C2 — Potentially dangerous. Urgent remedial action is required. Examples: no RCD protection on socket-outlet circuits, missing or ineffective earthing or bonding, damaged consumer unit. The risk is present but users are not in immediate danger.
What does C3 mean on an EICR?
C3 — Improvement recommended. The installation is safe for continued use but does not fully meet the current edition of BS 7671. C3 codes do NOT make the report Unsatisfactory.
What does FI mean on an EICR?
FI — Further investigation required without delay. The inspector found an apparent deficiency that could not be fully identified within the agreed extent and limitations, and which could turn out to be C1 or C2. FI always makes the report Unsatisfactory.
Does a C3 make an EICR Unsatisfactory?
No. Only C1, C2 or FI observations make the overall assessment Unsatisfactory. A report containing only C3s is Satisfactory — the installation is safe for continued use even though improvements would bring it closer to the current standard.
← All EICR guides · Generate an EICR PDF · When is the next one due?